АкушерствоАнатомияАнестезиологияВакцинопрофилактикаВалеологияВетеринарияГигиенаЗаболеванияИммунологияКардиологияНеврологияНефрологияОнкологияОториноларингологияОфтальмологияПаразитологияПедиатрияПервая помощьПсихиатрияПульмонологияРеанимацияРевматологияСтоматологияТерапияТоксикологияТравматологияУрологияФармакологияФармацевтикаФизиотерапияФтизиатрияХирургияЭндокринологияЭпидемиология

Equivalent polyphase circuits

Прочитайте:
  1. Exercise 6. Find corresponding equivalents
  2. Match the English sentences with their Russian equivalents. Define the forms of the Gerund (Indefinite/Perfect/Active/Passive). Analyze the methods of translating the Gerund.
  3. Match the English variant with Russian equivalents.
  4. Read the text “Integrated Circuits” and fill in the table.

Equivalent polyphase circuits could be realized by parallel or series connection of rectifier circuits:

- For reduction of pulsations of a waveform of Ud;

- For decrease of the higher harmonics of a waveform of i1;

- Those units are applied for high currents Id and high voltage Ud.

In a parallel way and in series way it is possible to connect different kinds of circuits: three-phase with center cap, with the current-balancing reactor, bridges. It is necessary to establish the phase displacement between secondary voltage and primary voltage in the angle depending of a number connected circuits for purpose setting up equivalent polyphase conditions.

 

1.13.1. S eries connection of two three-phase bridge rectifiers

Conditions: α=0, La=0, Ld=∞

 
 
       
   
 
 


Figure 1.42

 

 
 

 


 

 

Figure 1.43

 

Bridges I and II operate independently each from other. Transformers of ones are fulfilled with different group of transformer connections. In this case, in order to establish the phase displacement between outputs voltages of bridges, transformer connection for bridge I-Υ/Υ, for the bridge II – Δ/Υ. So waveforms of Ud1 and Ud11 are displaced on 30 degrees.

According to the aforesaid

UdI = UdII; Id = IdI = IdII; PdI = PdII.

 

For purpose of realization of these conditions, line voltage ratios of the transformers for both ones should be equal:

Secondary currents also are same:

Waveforms of primary phase currents also coincide with waveforms of secondary currents and, hence, coincide for bridges I and II, but its value differ one from other on times because as line KTr of both transformers are equal as phase KTr are differ

Thus, a peak primary phase current for winding connection Υ/Υ is and for Δ/Υ -

The primary current i1 is neighborhood of sine curve.

Primary windings could be connected in star, and secondary - one in a star, another in a delta then it is possible to use one transformer with two secondary windings.

Creation of similar circuits probably and with the big number of bridges but then it is necessary to use phase-shifting transformers. Sequential circuits are expedient for applying on the high voltage.

 

 